Enter configuration mode (password 0001). Navigate to FACt . Set to 1 . The unit will reset after 3 seconds.
Output relay chatters rapidly. Manual solution: Set P (proportional band) to a value greater than 0.5%. For ON/OFF control, set P = 0 and increase hysteresis ( Hyd ) to 2.0. Teqd-2301b Manual
Yes. The manual’s wiring diagram on page 12 shows terminals 5, 6, and 7 for RTD. The third wire compensates for lead resistance. Enter configuration mode (password 0001)
| Error Code | Meaning | Solution | |------------|---------|----------| | Err2 | Sensor open circuit | Check thermocouple continuity. Replace if broken. | | Err3 | Sensor reverse polarity | Swap the two sensor wires. | | Err4 | Input signal out of range | Verify 4-20mA loop is not shorted. | | Err5 | Output current overload | Reduce load; check for short across output relay. | | EE.rr | EEPROM write failure | Contact manufacturer – internal hardware fault. | Problem: Display shows “----” instead of temperature. Manual solution: The input type is mismatched. Confirm In.T matches your sensor. For a PT100, ensure you are using three-wire configuration. The unit will reset after 3 seconds
Yes – Appendix C lists all 32 holding registers, including PV (read-only at 0x0000) and SV (read/write at 0x0001).